A complete emergency power supply system is a reliable power generator and efficient, properly selected and configured automatic on reserve switching system.

 Depending on the type of control panels the GETOR ™ power generator has, two types of automatic on reserve switching systems that are available:

  • The systems of ATS-E type intended for cooperation with gensets equipped with AMF controllers, do not have a controller. Control cable for connecting the genset with the system cabinet – 11 × 1.5 mm2

 

  • ATS-I systems equipped with their own controller, dedicated to work with gensets equipped with an MRS controller. Control cable for connecting the genset with the system cabinet – 4 × 1.5 mm2

For both types of ATS systems, it is possible to connect auxiliary needs to the generator 3 × 2.5 mm2 or 5 × 2.5 mm2 depending on the power of the engine block heater.

As standard, the  Automatic switching on reserve systems up to 160A are made based on contactors, from 250A – a switch with a motor drive

CURRENT POWER MAX. WIRES
CONNECTION TYPE
DIMENSIONS MASS
A kVA mm2 width/height/depth (mm)
kg
60 42 35 screw coupling
400 x 500 x 200
18
100 70 35 screw coupling
400 x 500 x 200
25
135 93 35 screw coupling
400 x 500 x 200
25
160 111 50 screw coupling
600 x 800 x 300
55
250 173 2 x 70
single rail 25 x 5mm, M8
600 x 500 x 400
40
400 277 2 x 150
single rail 30 x 6 mm, M12
600 x 1000 x 450
75
630 436 2 x 240
single raila 40 x 8 mm, M12
600 x 1000 x 450
85
800 554 2 x 240
single rail 50 x 10 mm, M12
800 x 1000 x 550
85
1000 692 2 x 240
single rail 50 x 10 mm, M12
800 x 1600 x 600
180
1250 865 4 x 150
single rail 60 x 10 mm, M12
800 x 1600 x 600
210
1600 1107 4 x 185
double rail 50 x 10 mm, M12
1000 x 1800 x 800
340
2000
1384 4 x 240
double rail 80 x 10 mm, M12
1000 x 2000 x 800
360
2500 1730 8 x 240
double rail 100 x 10 mm, m12
1000 x 2000 x 800
370
3200 2214 8 x 240
triple rail 100 x 10, M12
1000 x 2000 800
420